Identify Panel
3-phase Panel
Split-phase Panel
Single-phase Panel
Are there breakers rated less than 60A?
Are there breakers rated greater than 60A?
The panel must have a neutral phase.
Cable colors
Scroll
Pull harder to load next
3-phase Panel
Split-phase Panel
Single-phase Panel
Are there breakers rated less than 60A?
Are there breakers rated greater than 60A?
The panel must have a neutral phase.
Cable colors
Next
Side of Panel
Junction Box
Next
Next
Tools you need to prepare
Parts you need to prepare
Next
Dry wall near panel (for recessed panels) There must be at least 15.5” x 5.5” x 5.5” space near the panel on drywall. In this section, the mounting plate for the Data Transmitter will be installed only. FWC installation will come at a later stage.
Next
Select one breaker per phase of panel to tap.
If you do not have one spare breaker on each voltage phase, you will need to briefly shut down the voltage tap breakers to complete this step. Please confirm with building operators that this will not interfere with operations or safety protocols. Please follow local jurisdiction requirements for tap installs.
If you do not have one spare breaker on each voltage phase, you will need to briefly shut down the voltage tap breakers to complete this step. Please confirm with building operators that this will not interfere with operations or safety protocols. Please follow local jurisdiction requirements for tap installs.
If there are no spare breakers, you can power the system from a wall plug. Strip the cable, to identify neutral and power, you do not need ground. Please confirm with building operators and follow local jurisdiction.
Ensure the breakers are turned off. Connect 1 voltage tap cable to breaker.
Ensure the breakers are turned off. Connect 2 voltage tap cables to breakers.
Ensure the breakers are turned off. Connect 2 voltage tap cables to breakers.
Wire The Neutral
Attach the white voltage tap cable to the neutral bar.
Route Wires
Route wires through knockout and into the FWC.
Next
CTs:
GIM:
Up to 3 Large CTs pair with each GIM.
Next
Clips CTs on circuits to be monitored. Make sure direction of load arrow on the CT points away from the breaker. Clearance required for adjacent CT installation.
Large CT and GIM
Insert CT wires into GIM terminals, match CT wire with GIM terminal colors.
Connect CT chain using extension cables and route wires through knockout into FWC.
Next
Next
Support data transmitter bottom until screws are secured from the top.
Slide open the bottom section of the data transmitter and find the indicator lights. Orient the data transmitter so that the indicator lights are visible.
Next
Turn breakers used for voltage tap on. The light ring will light up after up to 30 seconds.
Select the device that looks like your system.
A pulsing white light indicates that the system is properly installed and ready for commissioning.
The next step is to proceed with the commissioning process.
A pulsing red light indicates that the system has an error. Click here for details on service panel lights.
Select the error lights in the service panel that are red or yellow?
If there are multiple red and yellow lights please unplug the bud and replug it back in so it can reset.
What does the light look like?
There is a break in CT chain 2. Properly connected CT LEDs will be blinking white; excess CT LEDs will be off.
In the example above there is a break between the 2nd and 3rd CTs on the left. This can be an issue with the start of the cable in the 2nd CT or at the connector in the 3rd CT.
Fix this connection issue by removing and adding back in the 2nd and 3rd CTs. If this issue persists please reach out to support@verdigris.co.
There is a break in CT chain 1. Properly connected CT LEDs will be blinking white; excess CT LEDs will be off.
In the example above there is a break between the 2nd and 3rd CTs on the right. This can be an issue with the start of the cable in the 2nd CT or at the connector in the 3rd CT.
Fix this connection issue by removing and adding back in the 2nd and 3rd CTs. If this issue persists please reach out to support@verdigris.co.
System is performing chain check. Wait for LED indicator to change. System will cycle to check CT chain integrity every 10 seconds.
System is processing. CT chain indicator must be green first for LED indicator to change.
Two voltage phases and neutral detected.
Single voltage phase and neutral detected.
Three voltage phase and neutral detected.
Cannot connect to Internet, please connect to the system via your mobile device to debug wireless connectivity. (See page 20 of your installation manual).
Cannot connect to Internet, please press the reset button for 1second to bring up setup-tools and debug wireless connectivity. (See page 20 of your installation manual).
The system is busy.
Make changes to your system and then wait 30-120 seconds for the system to run tests again.
Did this resolve your issue?
We apologize that you are still experiencing issues. Please click here to speak with the Verdigris support team.